        Welcome to the website of Baoji Zhongheng Instrument Co., Ltd. Tel:+86-917-3512881
        Differential pressure transmitter Single crystal silicon pressure transmitter Electromagnetic flowmeter Capacitive pressure transmitter High precision pressure transmitter Intelligent pressure switch Diffused silicon pressure transmitter Flow switch Intelligent pressure transfer controller Thermometer

        Pressure transmitter


        BXY6001 Differential Pressure

        Product code

         

        Overview

        Product quotationProduct consulting

        Product introduction

        BXY6001- Differential Pressure Transmitter
        The BXY6001 differential pressure transmitter is used to measure the liquid level, density, pressure, and flow rate of liquids, gases, or vapors, and then convert it into a 4-20mADC HART current signal output. BXY6001 can also communicate with RST375 handheld terminal or RSM100 Modem for parameter setting, process monitoring, etc.
        Standard specifications
        (Calibrate the range based on the standard zero point, stainless steel 316L diaphragm, filled with silicone oil)
        1 Performance specifications
        Reference accuracy for range adjustment
        (Including linearity, backlash, and repeatability from zero)
        ± 0.075%
        If TD>10 (TD=maximum range/adjustable range), it is:
        ± (0.0075 × TD)%
        The square root output accuracy is 1.5 times the linear reference accuracy mentioned above
        Environmental temperature impact


        Range code

        -Total impact from 20 ℃ to 65 ℃

        A

        ±(0.45×TD+0.25)%×Span

        B

        ±(0.30×TD+0.20)%×Span

        C/D/E

        ±(0.20×TD+0.10)%×Span

        Range code

        -Total impact of 40 ℃~-20 ℃ and 65 ℃~85 ℃

        A

        ±(0.45×TD+0.25)%×Span

        B

        ±(0.30×TD+0.20)%×Span

        C/D/E

        ±(0.20×TD+0.10)%×Span

        Over range impact: ± 0.075% × Span
        Static pressure effect


        Range code

        influence quantity

        A

        ±(0.15%URL+0.10%Span)/4MPa

        B

        ±(0.10%URL+0.075%Span)/16MPa

        C/D/E

        ±(0.05%URL+0.05%Span)/16MPa

        Overvoltage effect

        Range code

        influence quantity

        A

        ±0.2%×Span/4MPa

        B

        ±0.2%×Span/16MPa

        C/D/E

        ±0.1%×Span/16MPa

        Long term stability

        Range code

        influence quantity

        A

        ±0.5%×Span/1year

        B

        ±0.2%×Span/1year

        C/D/E

        ±0.1%×Span/1year

        Power impact: ± 0.001%/10V (12-42V DC), negligible.
        2 Functional specifications
        Range and range



        Range/
        range


        kPa

        mbar

        A

        Range

        0.1~1

        1~10

        Range

        -1~1

        -10~10

        B

        Range

        0.2~6

        2~60

        Range

        -6~6

        -60~60

        C

        Range

        0.4~40

        4~400

        Range

        -40~40

        -400~400

        D

        Range

        2.5~250

        25~2500

        Range

        -250~250

        -2500~2500

        E

        Range

        20~2000

        0.2~20 bar

        Range

        -500~2000

        -5~20bar

        Range limit
        Within the upper and lower limits of the range, it can be adjusted arbitrarily.
        It is recommended to select range codes with the lowest possible range ratio to optimize performance characteristics.
        Zero point setting
        The zero point and range can be adjusted to any value within the measurement range in the table, as long as the calibrated range is ≥ the minimum range
        Installation position impact
        The change in installation position parallel to the film surface will not cause zero drift. If the installation position changes by more than 90 ° to the film surface, there will be zero drift within the range of<0.4kPa, which can be corrected by adjusting zero. No range impact.
        output
        2-wire system, 4-20mADC, selectable for digital communication with HART output, with options for linear or square root output.
        Output signal limit: Imin=3.9mA, Imax=20.mA
        Alarm current
        Low alarm mode (minimum): 3.7 mA
        High alarm mode (maximum): 21 mA
        No alarm mode (hold): maintain the effective current value before the fault
        Alarm current standard setting: high alarm mode
        response time
        The damping constant of the amplifier component is 0.1s; The sensor time constant is between 0.1 and 1.6 seconds, depending on the range and range ratio. The additional adjustable time constant is 0.1~60s.
        The impact on nonlinear output (such as square root function) depends on that function and can be calculated based on it.
        Preheating time:<15s
        ambient temperature
        -40-85 ℃
        When equipped with LCD display and fluororubber sealing ring, -20~65 ℃
        Storage temperature/transportation temperature
        -50-85 ℃; With LCD display: -40~85 ℃
        working pressure
        The rated working pressure is divided into three levels: 16MPa, 25MPa, and 40MPa
        Static pressure limit
        From an absolute pressure of 3.5kPa to the rated pressure, the protective pressure can be greater than 1.5 times the rated pressure and applied to both sides of the transmitter.
        Unidirectional overload limit: Unidirectional overload can reach rated pressure
        Electromagnetic compatibility (EMC)
        Refer to the "Electromagnetic Compatibility Schedule" on the next page
        3 Installation
        Power supply and load conditions
        The power supply voltage is 24V, R ≤ (Us-12V)/Imax k Ω
        Where Imax=23 mA
        Maximum power supply voltage: 42VDC
        Minimum power supply voltage: 12VDC, 15VDC (backlight LCD display)
        Digital communication load range: 250~600 Ω
        Electrical connections
        M20X1.5 cable sealing buckle and wiring terminal are suitable for wires ranging from 0.5 to 2.5mm2.
        Process Connection
        The two ends of the process connection flange have NPT 1/4 and UNF 7/16 internal threads.
        4 Physical specifications
        material quality
        Measurement capsule: stainless steel 316L
        Diaphragm: stainless steel 316L, Hastelloy C
        Process flange: stainless steel 304
        Nut and bolt: stainless steel (A4)
        Filling fluid: silicone oil
        Sealing ring: nitrile rubber (NBR), fluororubber

        Note: (1) A performance level description: During testing, the performance is normal within the technical specification limits.
        (2) B performance level description: During testing, the function or performance is temporarily reduced or lost, but it can recover on its own, and the actual operating status, storage, and data remain unchanged.
        External dimension unit (mm)
        Horizontal piping connection method (side) Horizontal piping connection method (front)