        Differential pressure transmitter Single crystal silicon pressure transmitter Electromagnetic flowmeter Capacitive pressure transmitter High precision pressure transmitter Intelligent pressure switch Diffused silicon pressure transmitter Flow switch Intelligent pressure transfer controller Thermometer

        Pressure transmitter


        BXY6002 gauge pressure BXY6003

        Product code

         

        Overview

        Product quotationProduct consulting

        Product introduction

        BXY6002 Gage Pressure Transmitter

        BXY6003- Absolute Pressure Transmitter
        The BXY6002/3-gauge/absolute pressure transmitter is used to measure the liquid level, density, and pressure of liquids, gases, or vapors, and then convert them into 4-20mADC HART current signals for output. BXY6002/3 can also communicate with RST375 handheld terminals or RSM100 Modems for parameter setting, process monitoring, etc.
        Standard specifications
        (Calibrate the range based on the standard zero point, stainless steel 316L diaphragm, filled with silicone oil)
        1 Performance specifications
        Reference accuracy for range adjustment
        (Including linearity, backlash, and repeatability from zero)
        ± 0.075%
        If TD>10 (TD=maximum range/adjustment range), then it is:
        ± (0.0075 × TD)%
        Environmental temperature impact


        Range code

        -Total impact from 20 ℃ to 65 ℃

        B/L

        ±(0.30×TD+0.20)%×Span

        other

        ±(0.20×TD+0.10)%×Span

        Range code

        -40℃~-20℃和65℃~85℃

        Total impact amount

        B/L

        ±(0.30×TD+0.20)%×Span

        other

        ±(0.20×TD+0.10)%×Span

        Over range impact: ± 0.075% × Span
        Long term stability


        Range code

        influence quantity

        B/L

        ±0.2%×Span/1year

        other

        ±0.1%×Span/1year

        Power impact
        ± 0.001%/10V (12-42V DC), negligible
        2 Functional specifications
        Range and range (BXY6002 gauge pressure)


        Range/Range

        kPa

        bar

        B

        range

        0.6~6

        6~60mbar

        range

        -6~6

        -60~60mbar

        C

        range

        2~40

        0.02~0.4

        range

        -40~40

        -0.4~0.4

        D

        range

        2.5~250

        0.025~2.5

        range

        -100~250

        -1~2.5

        F

        range

        30~3000

        0.3~30

        range

        -100~3000

        -1~30

        G

        range

        0.1~10MPa

        1~100

        range

        -0.1~10MPa

        -1~100

        H

        range

        0.21~21 MPa

        2.1~210

        range

        -0.1~21 MPa

        -1~210

        I

        range

        0.4~40 MPa

        4~400

        range

        -0.1~40 MPa

        -1~400

        J

        range

        0.6~60 MPa

        6~600

        range

        -0.1~60 MPa

        -1~600


        Range and Range (BXY6003- Absolute Pressure)

        Range and Range

        kPa

        bar

        L

        Range

        2~40

        0.02~0.4

        Range

        0~40

        0~0.4

        M

        Range

        2.5~250

        0.025~2.5

        Range

        0~250

        0~2.5

        O

        Range

        30~3000

        0.3~30

        Range

        0~3000

        0~30

        Range limit
        Within the upper and lower limits of the range, it can be adjusted arbitrarily. It is recommended to select range codes with the lowest possible range ratio to optimize performance characteristics.
        Zero point setting
        The zero point and range can be adjusted to any value within the measurement range in the table, as long as the calibrated range is ≥ the minimum range
        Installation position impact
        The change in installation position parallel to the film surface will not cause zero drift. If the installation position changes by more than 90 ° to the film surface, there will be zero drift within the range of<0.25kPa for range C, and zero drift within the range of<0.15kPa for other ranges. All can be corrected by adjusting zero. No range impact.
        Output
        2-wire system, 4-20mADC, selectable for digital communication with HART output, with options for linear or square root output.
        Output signal limit: Imin=3.9mA, Imax=20.mA
        Alarm current
        Low alarm mode (minimum): 3.7 mA
        High alarm mode (maximum): 21 mA
        No alarm mode (hold): maintain the effective current value before the fault
        Alarm current standard setting: high alarm mode
        Response time
        The damping constant of the amplifier component is 0.1s; The sensor time constant is between 0.1 and 1.6 seconds, depending on the range and range ratio. The additional adjustable time constant is 0.1~60s.
        Preheating time:<15s
        Environmental temperature
        -40-85 ℃
        When equipped with LCD display and fluororubber sealing ring, -20~65 ℃
        Storage temperature/transportation temperature
        -50-85 ℃
        With LCD display: -40~85 ℃
        Pressure limit
        From vacuum to maximum range.
        Overload limit:


        Range

        6kPa

        (B)

        40kPa

        (C/L)

        250kPa

        (D/M)

        3MPa

        (F/O)

        Overload limit

        0.2MPa

        1MPa

        4MPa

        16MPa

        Range

        10MPa

        (G)

        21MPa

        (H)

        40MPa

        (I)

        60MPa

        (K)

        Overload limit

        20MPa

        50MPa

        50MPa

        70MPa

        Electromagnetic compatibility (EMC)
        Refer to the "Electromagnetic Compatibility Schedule" on the next page
        3 Installation
        Power supply and load conditions
        The power supply voltage is 24V, R ≤ (Us-12V)/Imax k Ω
        Where Imax=23 mA
        Maximum power supply voltage: 42VDC
        Minimum power supply voltage: 12VDC, 15VDC (backlight LCD display)
        Digital communication load range: 230~600 Ω
        Electrical connections
        M20X1.5 cable sealing buckle and wiring terminal are suitable for wires ranging from 0.5 to 2.5mm2.
        Process Connection
        Standard process connection: NPT 1/2 internal thread, can be converted into NPT 1/2, G1/2, and M20x1.5 external thread, KF16 vacuum interface.
        4 Physical specifications
        material quality
        Diaphragm: stainless steel 316L, Hastelloy C
        Process connection: stainless steel 316L
        Filling fluid: silicone oil
        Transmitter housing: aluminum alloy material, with epoxy resin sprayed on the surface
        Shell sealing ring: nitrile rubber (NBR)
        Nameplate: stainless steel 304
        Weight
        1.6kg (without LCD display, mounting bracket, process connection)
        Shell protection level
        IP67
        Electromagnetic Compatibility Schedule



        External dimension unit (mm)
        Horizontal piping connection method (side) Horizontal piping connection method (front)


        Wall mounted connection method Vertical piping connection method

        5 Electrical connection diagram

        Note: The quick interface function is equivalent to the signal terminal.
        6 Process Connection Instructions (Code 1)
        6.1 Standard Form (Code 1)
        D/M/F/G/H/I/K/O Range Interface Diagram B/C/L Range Interface Diagram


        6.2 Derived interface form
        1/2 inch NPT external thread (code 2) M20x1.5 external thread (code 3)






























        ?